Pressure Reducing Regulator

SKU#:

Model 8310HP Differential

Description

Models 8310HP-1+6 and 8310HP-1+8 are differential reducing regulators used to maintain a relatively constant pressure differential between the fluid loading pressure – PLoad, and the valve’s outlet pressure – P2, with P2 pressure higher than PLoad pressure.

Model 8310HP-1+6 is a single-diaphragm differential construction. Model 8310HP-1+8 is a double-diaphragm differential construction. A double-diaphragm design prevents the fluid passing through the body from mixing into the loading fluid pressurizing the spring chamber in the event of a diaphragm failure. (See Figures 1 and 2).

The design takes advantage of all the features of the basic 8310HP double seated reducing regulator; see Technical Bulletin 8310-BASIC-TB. The availability of optional construction is limited to those indicated in this Technical Bulletin.

Inlet Design Pressure

  • 8310HP-1+6: 400 psig (27.6 Barg)
  • 8310HP-1+8: 400 psig (27.6 Barg)

Outlet Pressure

  • NORMAL OPERATION –
    • 8310HP-1+6: 175 psig (12.1 Barg)
    • 8310HP-1+8: 175 psig (12.1 Barg)
  • EMERGENCY OPERATION –
    • 8310HP-1+6: 200 psig (13.8 Barg)
    • 8310HP-1+8: 200 psig (13.8 Barg)

NOTE: Maximum safety relief device setpoint is not to exceed –
    8310HP-1+6: 1.10 x
    8310HP-1+8: 1.10 x
– the maximum Normal Outlet Pressure.

Line Sizes

  • 1-1/2" (DN40)
  • 2" (DN50)
  • 2-1/2" (DN65)
  • 3" (DN80)
  • 4" (DN100)

End Connections

  • NPT: 1-1/2" & 2" (DN 40 & 50) only
  • Opt-30: Integral Flanged
  • 125# Flgd: All body sizes, CI body, flat faced (FF)
  • 250# Flgd: All body sizes, CI body, raised faced (RF)
  • 150# Flgd: All body sizes, CS body, raised faced (RF)
  • 300# Flgd: All body sizes, CS body, raised faced (RF)
  • Opt-34: 14" Face to Face Flange
  • Dim. (CS - Sizes 1-1/2" & 2" only)

(Complies with ASME B16.4 and B16.34)

Material Combinations: Body / Spring Chamber

  • CI/DI
  • CS/CS

CI = Cast Iron 
DI = Ductile Iron
CS = Cast Carbon Steel 

More Information
Category Label Pressure Reducing Regulator
Service Gases, Liquids, Steam
Line Size 1.5" (DN40), 2" (DN50), 2.5" (DN65), 3" (DN80), 4" (DN100)
End Connections FNPT, Flanged, 14" Face to Face Flange
Process Applications Differential Pressure
Body Material Carbon Steel, Cast Iron
CV Tables
MODEL SIZE MAX CV MAX WORKING C V MIN CV SOFT SEAT MIN CV METAL SEAT FL FACTOR C1 MAX Cg
8310HP-1+6 1.5" 27 26.2 N/A 0.81 0.88 32.07 866
8310HP-1+6 2.0" 40 39.5 N/A 1.2 0.88 32.07 1283
8310HP-1+6 2.5" 55 55 N/A 1.65 0.88 32.07 1764
8310HP-1+6 3.0" 76 78 N/A 2.28 0.88 32.07 2437
8310HP-1+6 4.0" 100 100 N/A 3 0.88 32.07 3207